4.5.6 Heating/Cooling system
The actuator can be adapted to the given heating/cooling system by control parameters. The settings
are the same for heating and cooling:
Figure 30: Heating/cooling system
The following chart shows the dynamic range for this parameter:
Sub function
Dynamic range
[default value]
comment
Heating/Cooling system
Warm water heating
(5K/150min)
Underfloor heating
(5K/240min)
Split Unit (4K/90min)
Adjustment via control
parameter
Adjustment of the used
heating/cooling system.
Individual parameterizations
available by setting number 4
Proportional range
(K)
1K-8K
[2K]
If Adjust e t ia o t ol
pa a ete is sele ted fo the
heating/cooling system, the
proportional range can be chosen
freely
Reset time
(min)
15min
–
210 min
[150 min]
If Adjust e t ia o t ol
pa a ete is sele ted fo the
heating/cooling system, the reset
time can be chosen freely
Table 50: Heating/cooling system
The control parameter, proportional range and reset time, are adjusted by the setting for the
heating/cooling system.
It is possible to use predefined values, which fit to certain heating/cooling systems, or to
parameterize the proportional range and the reset time individually. The prederined values for the
belonging heating or cooling system are based on practical tested values and lead mostly to good
control results.
If a free Adjustment is chosen, proportional range and reset time can be chosen freely. This setting
needs enough knowledge at the area of control engineering.