Technichal Manual Heating Actuators AKH
MDT technologies GmbH •
51766 Engelskirchen
• Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
24
Furthermore it can be adjusted, whether a channel shall be integrated in the Heating/cooling
requirement and the maximum control value of the general settings:
Sub function
Dynamic range
[default value]
comment
Regard channel in
heating/cooling requirement
and max. control value
Yes
No
Adjustment whether the channel shall be
integrated in the calculation of the max.
control value and the heating/cooling
requirement.
Table 20: Heating/cooling requirement
If this setting is activated, the actuator will integrate this channel in the calculation of the max.
control value and the heating/cooling requirement.
You can adjust for every channel, whether a state object for the control value shall be shown or not.
Furthermore the sending conditions are selectable:
Sub function
Dynamic range
[default value]
comment
Send state control value
inactive
at changes
at enquiry
Adjustment, whether a state object of the
control value shall be shown and when it
shall send its actual value
Table 21: Send state control value
If this pa a ete is hose as i a ti e , o additio al o je t fo the state of the o t ol alue is
shown. At the setting sending at changes, the communication object sends the state of the control
value at every change. The setting sending at enquiry activates a passive state object. This object
sends its actual value only at a request.
The communication for the state of the control value has always the same size as the control value
itself:
Number
Name
Length
Usage
3
State control value
1 Bit
sends/responds the actual value of the control
value
Table 22: Communication object state control value