Technichal Manual Heating Actuators AKH
MDT technologies GmbH •
51766 Engelskirchen
• Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49
-2263-4588
• [email protected] • www.mdt.de
40
The following chart shows the hex values for the single messages:
Bit DPT HVAC Status
Hex-Value
0
Comfort
1=Comfort
0x01
1
Standby
1=Standby
0x02
2
Night
1=Night
0x04
3
Frost-/Heat protection
1= Frost-/Heat protection
0x08
4
5
Heating/Cooling
0=Cooling/1=Heating
0x20
6
7
Frost alarm
1=Frost alarm
0x80
Table 43: Hex-Values DPT HVAC Status
If you heat at the comfort mode, the communication object will send the value 20 (for heating) +1
(for the comfort mode) =21.
The DPT RHCC Status object is an additional 2 Byte status object with additional status messages. If
more than one testify is valid, also here the values will be added in the same way as at the HVAC
object.
The following chart shows the hex values for the single messages:
Bit
DPT RHCC Status
Hex-Value
0
Error Sensor
1=Error
0x01
8
Heating/Cooling
0=Cooling/1=Heating
0x100
13
Frost alarm
1=Frost alarm
0x2000
14
Heat alarm
1=Heat alarm
0x4000
Table 44: Hex-Values DPT RHCC Status
The Controller reacts always to the value, which was sent last. If you switched the operating mode
last via 1 Bit, the controller will react to the changeover by 1 Bit. If you switched the operating mode
last via 1 Byte, the controller will react to the changeover by 1 Byte.
The communication objects for the mode selection are shown at the following chart. The first 3
communication objects are for the 1 Bit changeover, the last 3 objects are for the changeover via 1
Byte:
Number
Name
Length
Usage
11
Mode Comfort
1 Bit
Activation of the mode comfort
12
Mode Night
1 Bit
Activation of the mode night
13
Mode Frost/Heat protection
1 Bit
Activation of the mode Frost/ Heat protection
25
DPT_HVAC Status
1 Byte
Visualization of the chosen operating mode
30
DPT_RHCC Status
2 Byte
Visualization measuring/ status of the controller
31
mode selection
1 Byte
Selection of the operating mode
Table 45: Communication objects for the operating mode changeover