ME30 infobox connect
22
infobox connect
16. Signalling function ISA 4A0
Corresponds to the first-up indication by single flashing light acc. to DIN 19235.
17. Signalling function ISA 4A1
In contrast to the first-up indication by single flashing light the gone messages which are not
first-up signals are not indicated (even if they are not yet acknowledged).
Message/pushbutton state
Indicator state
Int./ext.
Group message
Messages Pushb. operation
1st ind.
2nd ind.
horns
static
ackn.
dynam.
None
Not required
Off
Off
Off
Off
Off
Off
1st mess.
Not required
Fast
Off
On
On
On
On
arriving
flashing
2nd mess.
Not required
Fast
Steady light
On
On
On
Off/On
arriving
flashing
Pending
Horn ackn.
Fast
Steady light
Off
On
On
On
flashing
Pending
Message ackn.
Steady light Steady light
Off
On
Off
On
Going
Not required
Off
Off
Off
Off
Off
Off
Pending
Horn ackn.
Fast
Steady light
Off
On
On
On
flashing
Going
Not required
Fast
Off
Off
Off
On
Off
flashing
Gone
Message ackn.
Off
Off
Off
Off
Off
Off