ME30 infobox connect
24
infobox connect
19. Signalling function S05
Modified first-up indication by double flashing light: the first-up value is indicated by an
intermittend fast flashing light, all subsequent messages by an uninterrupted fast flashing light.
Also, first-up values and subsequent messages can still be distinguished after
acknowledgement.
Message/pushbutton state
Indicator state
Int./ext.
Group message
Messages Pushb. operation
1st ind.
2nd ind.
horns
static
ackn.
dynam.
None
Not required
Off
Off
Off
Off
Off
Off
1st mess.
Not required
Intermittent
Off
On
On
On
On
arriving
fast
flashing
2nd mess.
Not required
Intermittent
Fast
On
On
On
Off/On
arriving
fast
flashing
flashing
Pending
Horn ackn.
Fast
Steady light
Off
On
On
On
flashing
Pending
Message ackn.
Slow
Steady light
Off
On
Off
On
flashing
Going
Not required
Slow
Off
Off
Off
Off
Off
flashing
Gone
Delete
Off
Off
Off
Off
Off
Off
Pending
Horn ackn.
Intermittent
Fast
Off
On
On
On
fast
flashing
flashing
Going
Not required
Intermittent
Fast
Off
Off
On
Off
fast
flashing
flashing
Gone
Message ackn.
Slow
Off
Off
Off
Off
Off
flashing
Gone
Delete
Off
Off
Off
Off
Off
Off