![background image](http://html1.mh-extra.com/html/mauell/me30-infobox-connect/me30-infobox-connect_manual_1742264025.webp)
ME30 infobox connect
infobox connect
25
Message Indication / LED Outputs
Up to 40 messages can be indicated, depending on the type of device.
Programmable functions
a) Alarm indication:
Alarm messages are indicated by a red LED. The alarm messages are processed according to
the signalling mode configured (e.g., first-up indication by single flashing light).
b) Status indication:
There is no message processing with this function. Only the states of the message signals are
indicated (green LED).No acoustic signals (internal and external horn) are triggered.
Acknowledgement functions (horn, message, acknowledgement, Delete messages) are
therefore not required.
Range of application:
Message channel
Default setting:
Alarm indication
ON Delay for Messages
It is possible to delay the indication of a pending message. The message transmission to group
message contacts and optional relaying contacts is also delayed. Due to the time period
required for internal processing, the maximum basic delay can be 100 ms.
Range of application:
Message group
Default value:
0 ms (no ON delay)
Parameter range:
100 ms to 60 s
OFF Delay for Messages
Message indication and message contact are de-energized with a time delay.
Range of application:
Message group
Default value:
0 ms (no OFF delay)
Parameter range:
100 ms to 60 s