ME30 infobox connect
10
infobox connect
• Setting the Device Parameters
Use the two hexadecimally coded switches at the rear of the device to set the principal device
parameters . The boot loading function can also be triggered by a switch.
Baud Rates and Addresses
To achieve best communication through the device interface, you can adjust the baud rate so
that it matches the baud rate of the partner device. However, correct and safe data trans-
mission at baud rates higher than the default rate cannot be guaranteed. We therefore
recommend not to change the baud rate of the device.
Procedure:
- Switch off the device
- Set the switch for the required baud rate (see further down)
- Switch on device
- Wait for pulse tone of internal horn (This indicates that the baud rate is saved)
- Set the address of the device (red FA LED is on)
- Wait until the FA LED goes off again (valid address range: 1 to 7Fh)
The following baud rates can be set:
infobox connect with CAN
Switch Setting
Value for CAN
A0h to A3h
reserved
A4h
125 kbits/sec (default)
A5h
100 kbits/sec
A6h
50 kbits/sec
A7h
20 kbits/sec
A8h
10 kbits/sec
A9h to AFh
reserved
infobox connect with RS 232
Switch Setting
Value for RS 232
Switch Setting
Value for RS 232
A0h
reserved
A8h
1200 bits/sec
A1h
reserved
A9h
1050 bits/sec
A2h
9600 bits/sec (default)
AAh
600 bits/sec
A3h
7200 bits/sec
ABh
300 bits/sec
A4h
4800 bits/sec
ACh
200 bits/sec
A5h
2400 bits/sec
ADh
150 bits/sec
A6h
2000 bits/sec
AEh
134.5 bits/sec
A7h
1800 bits/sec
AFh
110 bits/sec