Soft ware Con fig u ra tion
In the
Edit-System Parameters
-{
PLC
} tab, configure as follows:
You must configure the OIT that connects to the PLC as the master. All other OITs should be configured as slave
OITs, unless an Ethernet switch is used, in which case the OITs may all be masters with separate local IP addresses,
and all have the same Server (PLC) address.
4
To configure Master OITs to talk with a PLC over the Ethernet port:
1.
Click on
Edit-System Parameters
and select the {
PLC
} tab.
2.
Select PLC Type as
Modbus RTU TCP/IP
.
3.
Select PLC I/F port as
Ethernet.
4.
For the multiple OIT box, select
Disable
if there are no slave OITs. Select
Master
if any OIT
is to be a slave unit, and, if so, select
Ethernet
for Connect I/F.
5.
Select a
unique IP Address
in the Local IP Address: boxes.
1010-1001a, Rev 02
74
Sil ver Se ries In stal la tion & Op er a tion Man ual
Summary of Contents for Silver HMI504T
Page 1: ...1010 1001A Rev 02...
Page 32: ...1010 1001a Rev 02 28 Silver Series Installation Operation Manual...
Page 128: ...1010 1001a Rev 01 124 Silver Series Installation Operation Manual...
Page 156: ...1010 1001a Rev 02 152 Silver Series Installation Operation Manual...
Page 166: ...1010 1001a Rev 02 162 Silver Series Installation Operation Manual...
Page 216: ...1010 1001a Rev 01 212 Silver Series Installation Operation Manual...
Page 251: ...1010 1001a Rev 02 Macros 247 Set Bit Objects Attributes Dialog Project Example of Add 2...
Page 264: ...End Macro_Command 1010 1001a Rev 02 260 Silver Series Installation Operation Manual...
Page 268: ...1010 1001a Rev 01 264 Silver Series Installation Operation Manual...