EN | 29 | ACX150/250 | Replacement interventions
© MAHLE
faults in the power board, running out of
the clock battery, faults in the micro SD
card, faults in the sensors, replacement is
required in case of:
Impossibility to correctly complete
card programming.
Incorrect display operation
Block in the acquisition and display
of the analogue signals not caused
by faults in the sensors or by a
miscalibration.
Incorrect activation of command
relays.
Wrong indications of the internal
clock not due to lack of adjustment
or running out of battery.
Evident damage to board
components and circuits.
For the replacement of the board it is
recommended to position the new board
alongside the one to be replaced.
Disconnect and reconnect the cables in
sequence one by one, please read as
reference the ATTACHMENT 3 –
ELECTRICAL CONNECTION – LOGIC
ELECTRONIC BOARD
Connect the ACX station to the PC via the
USB cable, start the CLIMAUPDATE
software and press the “tools” icon; right
after that, switch on the ACX station.
Enter the “DEBUG” password and
confirm.
Select the machine type in the pull-down
menu
Reprogram the machine with the updated
software
Select the language
Carry out gas scale calibration
Carry out pressure calibration
Enter the machine registration code
(it can be obtained through Mahle
website
www.arcticproacxregistration.com
by selecting the machine serial
number on which you are
operating).
Carry out the machine setup.
14.2.3
Replacement of electronic
power board
After having excluded any problem
regarding power supply, fuses on the
switch block, connection cables, faults in
the logic board, faults in the controlled
actuators, replacement is required in case
of:
Incorrect functioning of the power
supply unit section.
Summary of Contents for ACX150
Page 1: ...MAHLE ACX150 250 SERVICE MANUAL fflRHLE...
Page 3: ...EN 2 ACX150 250 Contents MAHLE 16 Diagnostic 30 16 1 Failure list 30...
Page 32: ...EN 31 ACX150 250 Diagnostic MAHLE ATTACHMENT 1 REFRIGERANT FLUID CIRCUIT ACX150 250...
Page 35: ...EN 34 ACX150 250 Diagnostic MAHLE Vacuum ACX150 250...
Page 36: ...EN 35 ACX150 250 Diagnostic MAHLE Oil injection ACX150 250...
Page 37: ...EN 36 ACX150 250 Diagnostic MAHLE Refrigerant recharge ACX150 250...
Page 83: ...DE 35 ACX150 250 Diagnose MAHLE ANHANG 1 REGELKREIS K LTEMITTEL ACX150 250...
Page 86: ...DE 38 ACX150 250 Diagnose MAHLE Vakuum ACX150 250...
Page 87: ...DE 39 ACX150 250 Diagnose MAHLE leinspritzung ACX150 250...
Page 88: ...DE 40 ACX150 250 Diagnose MAHLE Entladung K hlmittel ACX150 250...
Page 134: ...FR 34 ACX150 250 Diagnostic MAHLE ANNEXE 1 CIRCUIT DU LIQUIDE REFRIGERANT ACX150 250...
Page 137: ...FR 37 ACX150 250 Diagnostic MAHLE Vide ACX150 250...
Page 138: ...FR 38 ACX150 250 Diagnostic MAHLE Injection d huile ACX150 250...
Page 139: ...FR 39 ACX150 250 Diagnostic MAHLE R frig rant de recharge ACX150 250...
Page 150: ...FR 50 ACX150 250 Diagnostic MAHLE R FRIG RANT N EST PAS SUPPORT l analyseur...
Page 152: ...FR 52 ACX150 250 Diagnostic MAHLE...
Page 185: ...IT 33 ACX150 250 Diagnosi MAHLE ALLEGATO 1 CIRCUITO FLUIDO REFRIGERANTE ACX150 250...
Page 188: ...IT 36 ACX150 250 Diagnosi MAHLE Vuoto ACX150 250...
Page 189: ...IT 37 ACX150 250 Diagnosi MAHLE Iniezione olio ACX150 250...
Page 190: ...IT 38 ACX150 250 Diagnosi MAHLE Ricarica refrigerante ACX150 250...