IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
57
LED Operator Display
Fault Name
oFA30 to oFA43
Option Fault (Port A)
Communication ID Error.
Cause
Possible Solution
Option hardware fault
Replace the option.
LED Operator Display
Fault Name
oFb00
Option fault (CN5-B)
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to the
drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFb02
Option fault (CN5-B).
Two of the same options are connected at the same time.
Cause
Possible Solution
Options AI-A3 or D1-A3 were
connected to the CN5-B port while an
option was connected to CN5-A.
Only one type of AI-A3 or DI-A3 option can be connected to
the drive.
The SI-EP3 option can only be connected to CN5-A.
LED Operator Display
Fault Name
oFc00
Option Fault (CN5-C)
Non-compatible option is connected.
Cause
Possible Solution
Non-compatible option connected to the
drive.
Connect the correct option to CN5-A.
LED Operator Display
Fault Name
oFc02
Option Fault (CN5-C)
Two of the same options are connected simultaneously.
Cause
Possible Solution
Options AI-A3 or D1-A3 were
connected to the CN5-C port while an
option was connected to CN5-A.
Only one of these options, AI-A3, DI-A3, or SI-XX, can be
connected to the drive at the same time. The SI-N3 must be
connected to CN5-A.