IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
42
1018
Overspeed Det (oS)
•
Check reference and reference gain
•
Check F01-24 and F01-25 settings
1019
Speed Deviation (dEV)
•
Check load, accel/decel times, and system mechanics
•
Check F01-27 and F01-28 settings
101A
PG Open (PGO15)
Check PG card connections
101B
Input Phase Loss (PF)
Excessive input voltage fluctuation
101C
Output Phase Loss (LF)
•
Check for broken wire/loose terminals
•
Check motor rating
101D
None
--
101E
Operator Disconnected
(oPr)
Reconnect the digital operation
101F
EEPROM R/W Error (Err)
Cycle drive power and replace drive if fault continues
1020
None
--
1021
Comm Error (bUS)
•
Check network cable connections
•
Check 24 VDC power supply voltage
1022
Check option installation and connections
1023
Cycle drive power and replace option or drive if fault continues
1024
1025
Out of Control (CF)
•
Check motor parameters
•
Auto-tune
1027
External Fault 0 (EF0)
•
Check PLC program
•
Check MI switch setting
•
Check option LEDs for fault indication
Drive Alarm
Code (hex) <1>
Description
Corrective Action
<1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.