IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
59
Option Fault Monitors U06-98 and U06-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital
operator as shown in Table 31.
Table 31: Option Fault Monitor Descriptions
Two drive monitor parameters, U06-98 and U06-99, assist in network troubleshooting:
•
U06-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon
drive power-up.
•
U06-99 displays the present option SI-EP3 status. U06-99 is cleared upon a network-issued
fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U06-98 retains the original fault
value and U06-99 stores the new fault status value.
Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of
option. Refer to Table 32 for more information. More details can be found in the manual(s) for the
option(s) in question.
Table 32: Option Installation Compatibility
Fault Condition Fault Declared
Status Value
(U06-98/U06-99)
Description
No Fault
n/a
0
No faults.
Force Fault
EF0
3
Network sent a message to force this node to the
fault state.
Network Link
Down
BUS ERROR
1300
No network link to option board.
Network Failure
BUS ERROR
1301
Connection with PLC Timeout.
Default MAC
Address
Non
1303
Factory default MAC Address programmed into the
option. Return for reprogramming.
No IP Address
None
1304
No IP Address has been programmed into the
option.
No Station
Name
None
1305
No Station Name has been programmed into the
option.
Config Error
None
1306
Configuration error on power-up.
Init. Failure
None
1307
Initialize error on power-up.
Permanent
Communication
Loss
BUS ERROR
1308
Fatal error in MAC/PHY hardware, requires power
cycle to recover.
Option
Connector
Number of Possible Options
SI-C3, SI-N3, SI-P3, SI-S3,
SI-EP3, SI-EN3, SI-EM3 <1>
CN5-A
1
PG-B3, PG-X3
CN5-B, C
2 <2>
DO-A3, AO-A3, AI-A3, DI-A3
CN5-A, B, C
1
<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the
drive analog inputs with higher resolution. When installed in CN5-B or CN5-C, these options can only be used for
monitoring; their input levels will be displayed in U01-17 or U01-21 to U01-23.
<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when
connecting two options.