![background image](http://html1.mh-extra.com/html/magnetek/impulse-g-plus-series-4/impulse-g-plus-series-4_installation-manual_3663700022.webp)
IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
22
B03-02
<1>
Run Source 1
Source from where the RUN
command is generated.
0–3
1 (Set to 3 for
PROFINET)
0
Operator
Digital Operator
1
Terminals
Terminals
•
S4-IF Interface Card
•
S4-I AC Digital Input Option
•
S4-IO Digital Input/Output Option
•
DI-A3 Digital Input Option (not used for
B03-02)
2
Serial Com
Serial communication
•
RS485/422 Serial Communications
(R+, R-, S+, S-)
3
Option PCB
Industrial Communication Option
card (Port CN5-A)
•
EtherNet/IP
•
Modbus TCP/IP
•
PROFINET
•
PROFIBUS-DP
F06-01
Com Bus Flt Sel
Stopping method at
communication error.
0–4
1
0
Decel to Stop
1
Coast to Stop
2
Fast-Stop
3
Use B3-03 Method
4
Alarm Only <2>
F06-02
EF0 Detection
Option External Fault
0, 1
0
0
Always Detected
1
Only During Run
F06-03
EF0 Fault Action
Option External Fault
0–4
1
0
Decel to Stop
1
Coast to Stop
2
Fast-Stop
3
Use B3-03 Method
4
Alarm Only <2>
F06-07
Fref PrioritySel
Selects how multi-step speed
inputs are treated when the
NetRef command is set.
0, 1
0
0
Net/Com REF
Multi-step reference disabled
1
MultiStep Speed
Multi-step reference enabled
F06-08
Com Prm Init Sel
Determines whether
communication-related
parameters (F06-XX and F07-XX)
are reset when the drive is
initialized using A01-05
0, 1
0
0
Init Com Prms
Communication-related
parameters (F06-XX and F07-XX)
are not reset when the drive is
initialized using A01-05.
1
No Init Com Prms
Reset all communication-related
parameters (F06-XX and F07-XX)
when the drive is initialized using
A01-05.
Parameter
Code
Display
Function
Range
Initial Value
<1> To start and stop the drive with the option master device using serial communications, set B03-02 to 3. To control the drive frequency
reference via the master device, set B03-01 to 3.
<2> If F06-01 is set to 4: Alarm Only, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper
safety measures, such as installing an emergency stop switch.