IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
50
Email Alerts Tab
The Email Alerts tab allows the user to configure four Email Fault/Alarm conditions. When the
condition is true, one email will be sent to the provided email address. Another email will not be sent
until the condition becomes false and then true again. A 30-second timer prevents emails from being
sent when conditions reoccur immediately after being removed. The timer helps limit the amount of
emails sent regarding the same intermittent condition and helps to reduce network traffic by reducing
emails about reoccurring errors.
Figure 17: Email Alerts Tab View
Procedure: Conditional Email Set-up
1.
Define the condition that will trigger the email by selecting a monitor parameter, a comparator,
and a value. Set up comparator values for the range of values to check in the chosen condition.
If choosing only one condition and no OR or AND are needed, set the “OR/AND” drop-down
selection to “NotUsed”.
2.
Enter the email address where the alert will be sent.
3.
Enter the message that will appear in the email contents.
4.
Enter the email subject.
5.
Click the “Email Active” check box to enable the alert.
Clicking “Save to device” will save the entered information into the option memory.
Clicking “Cancel and reload” will cancel any pending edits and display the most recently saved
settings from the option board.