IMPULSE®•G+/VG+ Series 4 Profinet Installation Manual - August 2014
41
Fault Buffer Mechanism
The PROFIdrive profile has a mechanism that can store five fault situations to PROFIdrive
parameters. Fault and diagnostic data, like fault number and fault code, can be accessed
simultaneously with only one subindex. The mechanism consists of two PROFIdrive parameters:
•
PNU944: Fault message counter
•
PNU947: Fault numbers according to value in U02-01
Option High Priority Alarm Codes
These codes are transmitted as Manufacturer Specific Diagnostic high priority alarms that can be
seen in the PLC configuration software. These high priority codes are the same codes that appear in
the drive manual, except with an offset of 0x1000.
Table 25: PROFINET Option High Priority Alarm Codes
Drive Alarm
Code (hex) <1>
Description
Corrective Action
1000
None
--
1001
DC Bus Fuse Open (PUF)
Output Transistor Failure. Replace the drive.
1002
DC Bus Undervolt (Uv1)
Input power fluctuation too large.
1003
CTL PS Undervolt (Uv2)
Cycle drive power and replace drive if fault continues
1004
MC Answerback (Uv3)
Cycle drive power and replace drive if fault continues
1005
Short Circuit (SC)
•
Check drive wiring
•
Cycle drive power and replace drive if fault continues
1006
Ground Fault (GF)
Check for motor and/or cable damage
1007
Over Current (oC)
Check motor, motor load, and accel/decel rates
1008
DC Bus Overvolt (oV)
•
Check incoming voltage
•
Check deceleration time
1009
Heatsink Overtemp (oH)
•
Check ambient temperature
•
Check drive cooling fan
100A
Heatsink max Temp (oH1)
Check drive cooling fan
100B
Motor Overload (oL1)
•
Check the load, accel/decel, and cycle times
•
Check motor rated current (E02-01)
100C
Inv Overload (oL2)
•
Check the load, accel/decel, and cycle times
•
Check the drive rating
100D
Overtorque Det 1 (OT1)
•
Check L06-02 and L06-03 settings
•
Check system mechanics
100E
Overtorque Det 2 (OT2)
•
Check L06-05 and L06-06 settings
•
Check system mechanics
100F
DynBrk Transistor (rr)
Cycle drive power and replace drive if fault continues
1010
DynBrk Resistor (rH)
Check load, operating speed, and deceleration time
1011
External Fault 3 (EF3)
•
MFDI set to external fault
•
Circuit at terminal is closed
1012
External Fault 4 (EF4)
1013
External Fault 5 (EF5)
1014
External Fault 6 (EF6)
1015
External Fault 7 (EF7)
1016
External Fault 8 (EF8)
1017
Heatsink Fan (FAn)
Check drive cooling fan
<1> Drive error code is stored in MEMOBUS/Modbus address 0080 hex.