7.4 Accel/Decel time and pattern setting
Accel/Decel time setting based on Max frequency
7.4.1
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive group
ACC
[Accel time]
-
0 - 6000
5.0
Sec
dEC
[Decel time]
-
0 - 6000
10.0
Sec
Function
group 1
F21
[Max Frequency]
-
40 - 400
60.00
Hz
Function
group 2
H70
[Frequency Reference
for Accel/Decel]
0
0 - 1
0
H71
[Accel/Decel time scale]
-
0 - 2
1
Set the desired Accel/Decel time at ACC/dEC in Drive group.
If H70 is set to 0 {Max frequency}, Accel/Decel time is the time that takes to reach the
max freq from 0 Hz.
Desired Accel/Decel time unit is settable at the H71.
►
Accel/Decel time is set based on
F21
– [Max frequency]. For instance, if
F21
is set to
60Hz, Accel/Decel time 5 sec, and run frequency 30Hz, time to reach 30Hz would be
2.5 sec.