Basic Functions
Bas
ic
Fun
ctio
ns
7.7 Frequency limit
Frequency limit using Max Frequency and Start
7.7.1
Frequency
Group
Code
Parameter Name Setting Range Default Unit
Function group 1
F21
[Max frequency]
-
40 - 400
50.00
Hz
F23
[Start frequency]
-
0.1 - 10
0.50
Hz
Max Frequency: Frequency highest limit. Any frequency cannot be set above [Max
frequency] except for F22 [Base frequency].
Start Frequency: Frequency lowest limit. If a frequency is set lower than this, 0.00 is
automatically set.
Frequency command limit using High/Low limit
7.7.2
Group
Code
Parameter Name Setting Range Default Unit
Function group 1
F24
[Frequency high/low
limit select]
1
0 - 1
0
F25
[Frequency high
limit]
-
0 - 400
50.00
Hz
F26
[Frequency low limit] -
0 - 400
0.50
Hz
Set F24 to 1.
Active run frequency can be set within the range of F25 and F26.
►
When frequency setting is done via Analog input (voltage or current input), the inverter
operates within the range of high and low limit frequency as shown below.
►
This setting is also valid when frequency setting is done via keypad.
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...