50
Function list
Function group 2
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
H39
A327
[Carrier
frequency
select]
1 - 15
[kHz]
This parameter affects the audible sound
of the motor, noise emission from the
inverter, inverter temp, and leakage
current. If the set value is higher, the
inverter sound is quieter but the noise
from the inverter and leakage current will
become greater.
3
O
H40
A328
[Control mode
select]
0 - 2
0 {Volts/frequency Control}
0
X
1 {Slip compensation control}
H41
A329
[Auto tuning]
0 - 1
If this parameter is set to 1, it
automatically measures parameters of
the H42 and H44.
0
X
H42
A32A
[Stator
resistance
(Rs)]
0 - 28
[
]
This is the value of the motor stator
resistance.
-
X
H44
A32C
[Leakage
inductance
(L
)]
0-
300.0
[mH]
This is leakage inductance of the stator
and rotor of the motor.
-
X
H48
A330
PWM mode
select
0-1
If you want to limit a inverter leakage
current, select 2 phase PWM mode.
It has more noise in comparison to
Normal PWM mode.
0
X
0 Normal PWM mode
1 2 phase PWM mode
H49
A331
PID select
0-1
Selects whether using PID control or not 0
X
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...