208
6-) Connect the motor and fit the ferrite core ( output chokes ) as close to the inverter as
possible. Armoured or screened cable should be used with the 3 phase conductors only
threaded twice through the center of the ferrite core. The earth conductor should be
securely earthed at both inverter and motor ends. The screen should be connected to the
enclosure body via and earthed cable gland.
7-) Connect any control cables as instructed in the inverter instructions manual.
IT IS IMPORTANT THAT ALL LEAD LENGHTS ARE KEPT AS SHORT AS POSSIBLE
AND THAT INCOMING MAINS AND OUTGOING MOTOR CABLES ARE KEPT WELL
SEPARATED.
FF SERIES ( Footprint )
FE SERIES ( Standard )
INVERTER
FILTER
MOTOR
SHIELDED CABLE
FILTER
INVERTER
MOTOR
SHIELDED CABLE