Basic Functions
80
Operating command via FX, RX terminal 2
7.3.3
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive group
drv
[Drive mode]
2
0 - 4
1
I/O group
I17
[Multi-function input
terminal P1 define]
0
0 - 30
0
I18
[Multi-function input
terminal P2 define]
1
0 - 30
1
Set the
drv
to 2.
Set I17 and I18 to 0 and 1 to use P1 and P2 as FX and RX terminals.
FX: Operating command setting. Motor runs in forward direction when RX terminal (P2)
is OFF.
RX: Direction of motor rotation select. Motor runs in reverse direction when RX terminal
(P2) is ON.
Operating command via RS485 communication
7.3.4
Group
Code
Parameter Name
Setting
Range
Default Unit
Drive group
drv
[Drive mode]
3
0 - 4
1
I/O group
I59
[Communication protocol
select]
-
0 - 1
0
I60
[Inverter number]
-
1 - 250
1
I61
[Baud rate]
-
0 - 4
3
Set the
drv
to 3.
Set I59, I60 and I61correctly.
Inverter operation is performed via RS485 communication.
Refer to Chapter. 11. RS485 communication.