63
Function list
Fun
ctio
ns
List
5.5 Application Group
LED
display
Address
for
communi-
cation
Parameter
name
Min/
Max
range
Description
Factory
defaults
Adj.
during
run
Page
A1
1)
A501
[Sleep delay
time]
0-
2000
[s]
Sets a sleep delay time in PID drive.
20.0
O
A2
1)
A502
[Sleep
frequency]
0-400
[Hz]
Sets a sleep frequency when executing a
sleep function in PID control drive.
You can’t set more than Max.
frequency(F21)
0.00
O
A3
1)
A503
[Sleep Boost
Set]
0-100
[%]
Set the percentage of the PID reference
before entering sleep mode.
0.00
O
A4
1)
A504
[Sleep Boost
Time]
0-
1000.0
[s]
If the set time is exceeded, sleep mode is
entered.
0.0
O
A5
1)
A505
[Wake up
Delay Time]
0-
6000.0
[s]
Sets a Wake Up delay time in PID drive.
20.0
O
A6
1)
A506
[Wake up
level]
0-
100.0
[%]
Sets a wake up level in PID control drive. 20.0
O
A7
1)
A507
[Pre-PID Mode
Freq]
0-400
[Hz]
Sets the frequency range for a general
acceleration without PID control.
0.00
O
A8
1)
A508
[Pre-PID Exit
Level]
0-
100.0
[%]
When the feedback exceeds the Pre-PID
Exit Level, the Pre-PID operation ends and
a normal process PID operation begins.
20.0
O
A9
1)
A509
[Pre-PID
Timer]
0-
100.0
[s]
When the time exceeds the Pre-PID
Timer, the Pre-PID operation ends and a
normal process PID operation begins.
60.0
O
A11
1)
A50B
[MMC Sel]
0-1
Selects the MMC operation settings.
0
X
0 No: Deactivates MMC function
1 Yes : Activates MMC function
A12
2)
A50C
[Num Of Aux]
1-2
Decides the number of auxiliary motors to
use.
2
O
A13
2)
A50D
[Start Freq1]
A15-
400
[Hz]
Sets the auxiliary motor start frequency.
40.0
O
A14
2)
A50E
[Start Freq2]
A16-
400
[Hz]
Sets the auxiliary motor start frequency.
40.0
O
A15
2)
A50F
[Stop Freq1]
0-A13
[Hz]
Sets the auxiliary motor stop frequency.
20.0
O
A16
2)
A510
[Stop Freq2]
0-A14
[Hz]
Sets the auxiliary motor stop frequency.
20.0
O
A17
2)
A511
[Aux Start
Delay Time]
0.1-
600.0
[s]
The auxiliary motors turns on or off after
the auxiliary motor stop delay time
elapses.
5.0
O
1)
: Set H49 to 1 (PID control) to display this parameter.
2)
: Set A11 to 1 (MMC Select) to display this parameter.
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...