85
Basic Functions
Bas
ic
Fun
ctio
ns
Multi-Accel/Decel time setting via Multi-function terminals
7.4.3
Group
Code
Parameter Name
Setting Range Default Unit
Drive
group
ACC
[Accel time]
-
0 - 6000 5.0
Sec
dEC
[Decel time]
-
0 - 6000 10.0
Sec
I/O
group
I17
[Multi-function input terminal P1 define] 0
0 - 30
0
I18
[Multi-function input terminal P2
define]
8
1
I19
[Multi-function input terminal P3
define]
9
2
I34
[Multi-Accel time 1]
-
0 - 6000
3.0
Sec
-
-
I39
[Multi-Decel time 3]
-
5.0
Set I18, I19 to 8, 9 if you want to set Multi - Accel/Decel time via P2-P3 terminals.
Multi-Accel/Decel time 0 is settable at ACC and dEC.
Multi-Accel/Decel time 1-3 is settable at I34-I39.
Accel/Decel time
P2
P3
0
-
-
1
-
2
-
3
www.barghmaher.ir