RS485 communication
180
Note
When Request for Write and Acknowledge Response is exchanged between PC and
Inverter for the first time, previous data is returned. From the second time of
transmission, the current data will be returned.
2.2) Negative response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” - “1F”
“W”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bite = 9
3)
Request for Monitor Register
This is useful when constant parameter monitoring and data updates are required.
Request for Register of
‘n’ numbers of Address (not consecutive)
ENQ
Drive No
CMD
Number of
address to read
Address
SUM
EOT
05h
“01” - “1F”
“X”
“1” - “8”=n
“XXXX…”
“XX”
04h
1 byte
2 bytes
1 byte
1 byte
n * 4 byte
2 byte
1 byte
Total bite = 8 + n * 4 = Max 40
3.1) Acknowledge Response:
ACK
Drive No
CMD
SUM
EOT
06h
“01” - “1F”
“X”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
1 byte
Total bite = 7
3.2) Negative Acknowledge Response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” - “1F”
“X”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bite = 9
4)
Action Request for monitor register: Request for read of address registered by
monitor register.
ENQ
Drive No
CMD
SUM
EOT
05h
“01” - “1F”
“Y”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
1 byte
Total bite = 7
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...