Advanced functions
115
Adv
anc
ed
Fun
ctio
ns
Auto Change is activated when auxiliary motors are in the operating state over time of A24
and then every auxiliary motor is stopped and the inverter operation frequency is below the
frequency set at A25.
Note
Start order and stop order of the auxiliary motors are based on the order set at
A22(FIFO/FILO).
The following diagrams depict the auxiliary motor start and stop sequence, based on a FILO
configuration, when the inverter operation time exceeds the auto change interval set at A24. If
all the auxiliary motors are turned off and the inverter operation frequency is below the
frequency set at A25 (Auto Ch Level), auto change is operated. Then, when the inverter
frequency increases due to decrease in the feedback, auxiliary motor #2 starts instead of
auxiliary motor #1 due to this auto change (auxiliary motor #1 starts last, for it has the lowest
priority).