Advanced functions
136
8.29 Accel/Decel Change Frequency
This function is to use a different ACC/DEC time starting from a set frequency.
At start, up to A37_Start&End Ramp frequency, the motor accelerates a normal time
and from A37 frequency, ACC time references A35_StartRampAcc.
During decel stop, A36_EndRampAcc is referenced until A37 frequency and normal
deceleration time is applied.
Group
Code
Parameter Name
Setting
Range
Default Unit
Application
Group
A35
StartRampAcc
-
-0-6000
10.0
sec
A36
EndRampDec
-
-0-6000
10.0
sec
A37
Start&End Ramp
-
-0-Max Freq.
0.00
sec
•
The inverter operates at the slope set at A35, A36 below the Start&End Ramp
frequency set at A37 of the operating frequency. However, if the operating
frequency rises over the Start&End Ramp, the inverter runs at the Acc/Dec slope
set at ACC, DEC in the drive group.
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...