RS485 communication
179
Com
munic
ation
Detail communication protocol
1)
Request for Read: Request for read successive
‘N’ numbers of WORD from
address
“XXXX”
ENQ
Drive No
CMD
Address
Number of
address to read
SUM
EOT
05h
“01” -
“1F”
“R”
“XXXX”
“1” - “8” = n
“XX”
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
2 bytes
1 byte
Total bite = 12
The quotation marks (
“ ”) means character.
1.1) Acknowledge Response:
ACK
Drive No
CMD
Data
SUM
EOT
06h
“01” - “1F”
“R”
“XXXX”
“XX”
04h
1 byte
2 bytes
1 byte
N * 4 bytes
2 byte
1 byte
Total bite = 7 + n * 4 = Max 39
1.2) Negative Acknowledge Response:
NAK
Drive No
CMD
Error code
SUM
EOT
15h
“01” - “1F”
“R”
“**”
“XX”
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bite = 9
2)
Request for Write:
ENQ
Drive No
CMD Address
Number of
address to
read
Data
SUM
EOT
05h
“01”- “1F”
“W”
“XXXX”
“1” - “8” = n
“XXXX…”
“XX”
04h
1 byte
2 bytes
1 byte 4 bytes
1 byte
n * 4 bytes
2 byte
1 byte
Total bite = 12 + n * 4 = Max 44
2.1) Acknowledge response:
ACK
Drive No
CMD
Data
SUM
EOT
06h
“01” - “1F”
“W”
“XXXX…”
“XX”
04h
1:byte
2:bytes
1:byte
n * 4 bytes
2 bytes
1 byte
Total bite = 7 + n * 4 = Max 39
www.barghmaher.ir
Summary of Contents for iG5H Series
Page 13: ...www barghmaher ir ...
Page 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Page 23: ...10 Installation Wiring www barghmaher ir ...
Page 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Page 173: ...Protective functions 160 www barghmaher ir ...
Page 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Page 223: ...210 www barghmaher ir ...