To set siren cut-off:

1. From the main menu, select 

Programming”→

#”

→ Device”→

#”

→ Siren”→

#”

→ Siren Cut-off(M)

 

2. Input the period 

0-30minutes

”.

3. Press 

“#” 

to

 

exit

.

Wireless Zone Supervision

Wireless devices will transmit supervision signal to the control panel at intervals. If the system does not 
receive  any  signal,  then  the  transmitter  is  regarded  as  loss.  The  max  loss  period  is  called  supervision 
time.  If  no  signal  is  transmitted  during  this  period,  wireless  zone  trouble  appears  in  the  list  of  system 
trouble.
To set wireless zone supervision:

1. From the main menu, select 

Programming”→

“#”

Device”→

“#“

WL. Superv.”→

“#”

SV ON/OFF

     

2.  Press

 

the

 

navigation

 

key

 

to

 

select

 

ON

 

or

 

OFF

 

ending

 

with

  “ #” . 

And

 

then

 

set

 

the

 

supervision  time.

3. Press the navigation key to select 

Superv. Time(Hr)

.

4. Input the time(1-99hours)

5. Press 

“#” 

to confirm and then “

*

  

to exit

.

8.3.8.2 Communication

“#”.

“#”

“#”

CMS Phone Set

CMS(Central  Monitor  Station)  is  used  for  event  upload  through  phone  network,  including  alarm,  arm  & 
disarm, system trouble and service event log, etc., of which the phone number can be edited or deleted.
To set CMS phone:

1. From the main menu, select 

Programming”

→ Comm.”

→Comm. Account

” 

 “#”.

2. Press the navigation key to select CMS 1 or CMS 2 ending with 

“#”.

3. Then press the navigation key to select 

Phone NO.

” 

to

 

enter

 

with

 “#”.

4. If any phone number is set already, it will display on the LCD. Press 

“#” 

to

 

input

 

with

 

the

 

icon

 

flash

If

 

no

 

    phone

 

number

 

is

 

set

 

before

input

 

directly

.

5. The phone number is 16 digits utmost ending with 

“#”. 

Press

 “

*

” 

to

 

delete

 

former

 

digit

 

or

 

edit

 

it

Press

 “#” 

    to

 

confirm

If

 

press

 “#’ 

directly

the

 

former

 

phone

 

number

 

will

 

be

 

deleted

.

CMS Event Option

The options are: send for alarm,  send for arm & disarm, send for system trouble, send for service info. If 

the function of 

Send for Alarm

” 

is

 

closed

the

 

alarm

 

info

 

will

 

not

 

be

 

sent

 

to

 

CMS

If

 

the

 

function

 

of

 “

Send for 

Arm/Disarm

” 

is

 

closed

the

 

arm

 

or

 

disarm

 

operation

 

will

 

not

 

be

 

sent

 

to

 

CMS and “cancel alarm” is invalid

If

 

the

 

function

 

of

 “

Send for Trb

.” 

is

 

closed

the

 

trouble

 

info

 

will

 

not

 

be

 

sent

If

 

the

 

function

 

of

 “

Send for service

” 

is

 

closed

the

 

trouble

 

info

 

will

 

not

 

be

 

sent during enter ir quit programming or zone bypass

.  

It

 

will

 

send

 

all

 

event

 

as

 

default

.

“#”

“#”

-39-  

-40-  

To send for alarm:

1.  From the main menu, select  Programming”

Comm.”

Comm. Account

#”

” 

“#”.

2.  Press the navigation key to select CMS 1 or 2, ending with 

Then press the navigation key to select

“#”. 

 

 

 

 

 

 

 

      Event Option ending with

” 

 

 “#”.

3.  Press the navigation key ro select 

ending with

Send for Alarm

” 

 

 “#”.

4.  Press the navigation key to select  ON or OFF ending with

”   “

” 

 

 “#”.

5.  Press 

to exit

“#”   

.

 

  

 

 

 For

 

others

operate

 

as

 

above

.

SMS Center Number

SMS center uploads event log through GSM network, which includes alarms, arm &disarm, system trouble, 
event log and service info. The phone number can be edited or deleted.
To set SMS center number:

1.  From the main menu, select  Programming”

Comm.”

Comm Account ending

“#“

“#”

” 

 

    with

 

 “#”.

2.  Press the navigation key to select SMS center 1 or 2, ending with 

“#”.

3.  If any number is set before, it will display on the LCD. Press 

the icon will flash for figure input

while

“#”, 

 

 

 

 

 

 

     no number is set you can input directly with icon indication

 

 

   

 

 

 

 

 

 

.

4. The phone number is 16 digits utmost ending with 

Press

to delete former digit or edit it Press

“#”. 

 “

*

”   

 

 

 

 

  . 

 “#” 

     to confirm If press

directly the former phone number will be deleted

 

.   

 “#’ 

 

 

 

 

 

 

.

“#”

 

end mes sage to CMS

 

for alarm:

1.  From the mai n men u, select 

Programmi ng”→

“#”

Comm. ”→

“#”

Comm. Account

” 

“#”.

2.  Press the navigation key to select SMS center 1 or 2, ending with 

“#”. 

And

 

then

 

press

 

the

 

navigation key

 

    

 

to

 

select

 “

Event Opt ion

” 

ending

 

with

 “#”.

3.  Press the navigation key to select 

Send for Alarm

” 

ending

 

with

 “#”.

4.  Press the navigation key to select 

ON

” 

or

 “

OFF

” 

ending

 

with

 “#”.

5.  Press 

*

” 

to

 

exit

.

      

To s

SMS Even t Opti on

Voice Ph one Interface Se t

SMS center event option includes: send for alarm, send for arm & disarm, send for system trouble, send  

for service info. If “Send for Alarm” is closed, the alarm info will not be sent to CMS. If the function of “Send 

for Arm/Disarm” is closed, the arm or disarm operation will not be sent. If the function of “Send for Trb.” is 

closed, the trouble info will not be sent. If the function of “Send for Service Info” is closed, the info will not 

be sent during enter or quit programming or zone bypass. It will send all event as default. 

Summary of Contents for LHD8003

Page 1: ...86 755 33265388 Website http www csst longhorn com E mail helen p csst com TH ST TH THE 4 BUILDING 1 FLOOR OF THE 5 BUILDING NEW AND HIGH TECHNOLOGY PARK GUANGMING WANDAIHENG BAOAN SHENZHEN CHINA LHD...

Page 2: ...CREATING SECURITY SOLUTION...

Page 3: ...Address CMS 2 Phone NO SMS Center 1 SMS Center 1 Address SMS Center 1 Phone NO SMS Center 2 SMS Center 2 Address SMS Center 2 Phone NO 02 PACKING LIST Note It should include screws 4pcs EOL resistanc...

Page 4: ...1 2 Arm Stay 5 5 6 6 7 7 8 8 8 9 9 10 10 12 13 13 13 14 14 15 15 15 15 16 18 19 19 20 21 22 22 22 23 23 23 24 7 1 3 Disarm 7 2 Arm Disarm via Phone 7 3 Arm Disarm via SMS 7 4 Trigger Alarm via Keypad...

Page 5: ...lay intelligent voice guide operation Periodic supervision for wireless PIR and magnetic switch PSTN or GSM dialing or SMS message send for alarm optional Upload and download function optional 255 eve...

Page 6: ...ng guidelines 1 Whenever possible mount the panel centrally in relation to wireless sensors 2 Avoid installation in close proximity to sources of high noise or radio frequency interference for example...

Page 7: ...wireless detector magnetic switch siren and keyfobs etc Step 6 Test the communication signal of chosen mounting location Step 7 Permanently install the control panel and transmitters Figure 5 TX TX R...

Page 8: ...adaptor and plug the backup battery The control panel can not be initialized by only battery Parameters of power adaptor Input 100V 240VAC 50 60HZ 0 5A Output 12VDC 1 5A Backup battery 7 2V 1800mAh Ni...

Page 9: ...ct attention to the depth of screws to make sure easy hang and tamper switch work normally There are 2 tamper switches front tamper and rear tamper Compress the tamper switch while installing If the c...

Page 10: ...g symbols or marks Selected for multiple choice Unselected for multiple choice Selected for single choice Unselected for single choice Counting down System trouble Display of alarm events Alarm List S...

Page 11: ...ent alarm way 1 For entry exit zone only during arm away and arm stay will the zone be triggered with alarm delay 2 For active zone only during arm away will the zone be triggered with alarm delay 3 W...

Page 12: ...will auto release the code While if the code is locked after alarm auto release must be available after system re intialization or within 30 minutes If the code is input wrong the voice will guide Wr...

Page 13: ...alance for SIM card Commu nication Trouble Trouble There are 8 types of zones entry exit zone active zone perimeter zone panic zone fire zone gas zone tamper zone and duress zone There are 22 zones zo...

Page 14: ...ng Arm or disarm is not available during programming or trouble query Via keypad requires installer code while via keypad requires no code Exit Delaying s When the exit delay ends the voice guide will...

Page 15: ...isarmed alarm log eliminated 2 Disarm with alarm status saved Input the code except installer code ending with just the arm LED turns from Red to Green with voice guide Disarmed Disarm 2 0 1 2 2 0 1 0...

Page 16: ...r confirm Press to quit programming to previous menu Or it will return to previous automatically with no operation within 1 minute 27 28 Through this operation all communication buffers are cleared an...

Page 17: ...confirm or press to quit To set duress code 1 From the menu select Code Set Duress Code Duress Code Set While you disarm with duress code it will indicate Disarm on site but will dial or send alarm in...

Page 18: ...digits utmost Press to finish Or if no figure is input and is pressed directly the number will be deleted Voice Phone Interface Set It enables you to select PSTN or GSM as dialling way To set voice ph...

Page 19: ...n finished Siren test is strongly recommended periodically for safety which includes wired siren wireless siren and built in siren To test siren 1 From the menu select Service 2 Press the navigation k...

Page 20: ...it is registered the info will display on LCD If it isn t registered it will indicate as unknown signal 4 Press to quit after test finish GSM Test To ensure the validity of GSM communication please te...

Page 21: ...21 22 wired zones Zones No 17 and 19 To set siren function 1 From the main menu select Programming Device Zone Zone Siren Set 2 Use the navigation key to select the zone ending with 3 Then use naviga...

Page 22: ...nt If the function of Send for service is closed the trouble info will not be sent during enter ir quit programming or zone bypass It will send all event as default 39 40 To send for alarm 1 From the...

Page 23: ...ttempts option determines the number of times the system tries to call a telephone number before moving on to the next number in sequence It will not dial again if it exceeds the attempts Comm To set...

Page 24: ...tion Exit Delay S System 2 Press to edit with icon indication 3 Set the exit delay 0 300s 4 Press to finish and to exit Supplementary Entry Delay The Supplementary Entry Delay is a pre alarm feature t...

Page 25: ...While before the message is sent to the station and the telephone line recovers connected well the message will be cancelled Or if the message for Line loss is sent to the station successfully before...

Page 26: ...rm stay press 2 for disarm press 3 For alarm press 5 Turn on site siren press 6 turn off site siren press 7 for hang up please press 0 repeat Chapter 9 Telecontrol via Phone or SMS Pressing any key du...

Page 27: ...to the set phone number or SMS center for alarm or system trouble through Contact ID For example the control panel ID is 1234 when fire alarm disarm or zone trouble occurs it will send SMS as followi...

Page 28: ...et the incorrect telephone number User telephone is busy during alarm Few ringing attempts lead the system to hang up the phone automatically Battery is drained Enroll remote controller without progra...

Page 29: ...tenance may lead to the system disable Weekly testing is necessary to ensure the system work normally Chapter 12 Warranty and Limitations 53 54 Appendix 1 System Default Parameters No Setting Item Par...

Page 30: ...Ent Delay Output Trigger PGM Cut off Clear Users Del Superv SV CMS SMS Zone Trb Ind Call Back Reg Dis En Ex Per Line Loss TX Interface Auto ON OFF Wired Test WL Test Built in Test Clear WL Clear Sing...

Page 31: ...Zone 1 WL Register 1 By Code Learn 2 By Code Input 2 Clear WL 1 Clear Single 2 Clear All 3 Set zone Type 5 Chime Zone Set 4 Zone Siren Set 2 Keyfobs 1 Keyfob Register 1 By Code Learn 2 By Code Input...

Page 32: ...e entry exit zones active zones perimeter 24 hour zone No matter armed or disarmed it is in valid detecting status It is usually used in fire alarm duress alarm and other emergent alarm which can be c...

Page 33: ...Appendix 5 Zone Type Setting Figure Zone NO Installation Position Type Bypass or not 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 61...

Reviews: