49
4.4.2
Terminal A2 Voltage/Current Input Selection
Select voltage or current input at terminal A2
To select current as the input type, set DIP switch A2 to I and set parameter E3-06 to 0 (0 to 20
mA) or 1 (4 to 20 mA).
To select voltage as the input type, set DIP switch A2 to V and set parameter E3-06 to 2 (0 to 10
V) or 3 (0 to 5 V).
F1-F4
F5-F6
Figure 4.4.2 DIP Switch A2
V I