80
Parameter
Name
Description
Setting Range
2
∶
Accept the Up/Down frequency at stop
L4-01 <4>
Frequency
Command Bias
(Up/Down 2)
Sets the bias used to add to or subtract from the
frequency command by Up/Down 2.
Default:0.00 Hz
Min.: 0.00 Hz
Max.: 99.99 Hz
L4-02 <4>
Frequency
Command Acc./Dec
Setting (Up/Down
2 )
Sets the acceleration/deceleration times to
increase or decrease the frequency command bias
for Up/Down 2.
0 : Current Acc./Dec. Time
1 : Acc./Dec. Time 4 set in C1-06 and C1-07
Default: 0
Range: 0, 1
L4-03 <4>
Up/Down
Frequency
Command Save
Saves the frequency command from Up/Down 1
or Up/Down 2
Default: 0.00Hz
Min.: 0.00 Hz
Max.: <5>
L4-04
Frequency
Command Save
0: Disabled
1: Enabled
Default: 0
Range 0, 1
L5
:
Torque Control
L5-00
Torque Command
Delay Time
Apply a filter with the time constant set to
parameter d5-02 to the torque reference signal to
eliminate oscillation resulting from an unstable
torque reference signal. Increase the setting when
oscillation occurs during torque control.
Default : 0 ms
Min.
∶
0 ms
Max.
∶
1000 ms
L5-01 Speed Limit Selection
Selects the speed limit for Torque Control.
1
:
Frequency Command
(Refer to the b1-00 and b1-07 settings)
2
:
L5-02 and L5-03
Default
∶
1
Min.
∶
1
Max.
∶
2
L5-02 Forward Speed Limit
Sets the forward speed limit during Torque Control
as a percentage of highest speed when L5-01 = 2.
Default
∶
10 %
Min.
∶
0 %
Max.
∶
120 %
L5-03 Reverse Speed Limit
Sets the reverse speed limit during Torque Control
as a percentage of highest speed when L5-01 = 2.
Default
∶
10 %
Min.
∶
0 %
Max.
∶
120 %
L5-04
Speed/Torque
Control Switch
Delay Time
Sets the delay time for switching between Speed
Control and Torque Control. This function is
enabled when sets the speed of multi-function
input and the switching of Torque control are valid
Default
∶
0 ms
Min.
∶
0 ms
Max.
∶
1000 ms
L5-05 Retain
L5-06
<7>
Torque command
delay time 2
Set the one-time delay constant of the torque
command filter in ms, and eliminate the vibration
caused by the speed reaching speed limit. When
the torque control generates vibration due to the
Default
∶
10 ms
Min.
∶
0 ms
Max.
∶
1000 ms
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...