69
Parameter
Name
Description
Setting Range
2
∶
Feedback Low /High Fault
A fault will cause the drive to stop the motor.
3
∶
Multi-Function Output only when PID is
Disabled
Same action as b5-11=0.
4
∶
Feedback Low /High Alarm (detection disabled
when PID is disabled)
5
∶
Feedback Low /High Fault (detection disabled
when PID is disabled)
6 : Multi-function output, no light faults continue
to operate
7 : Multi-function contacts only (non-operational
detection is still valid)
b5-12
PID Feedback Low
Detection Level
Sets the PID feedback level used for detection.
When the PID feedback falls below this level for
longer than the time set to b5-13, PID feedback
loss will be detected.
Default
∶
0%
Min.: 0%
Max.: 100%
b5-13
PID Feedback Low
Detection Time
Sets the PID feedback time used for detection.
When the PID feedback falls below the level set to
b5-12 for longer than this time, PID feedback loss
will be detected.
Default
∶
1.0 s
Min.: 0.0 s
Max.: 25.5 s
b5-14
PID Sleep Start
Level
Sets the PID level to trigger the drive to sleep.
Default
∶
0.0Hz
Min.: 0.0 Hz
Max.: <5>
b5-15
PID Sleep Delay
Time
Sets the delay time used to activate/deactivate
the PID Sleep function.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 25.5 s
b5-16
PID Command
Acc./Dec. Time
Sets the PID command acceleration /deceleration
time used for PID target.
Default
∶
0.0 s
Min.: 0.0 s
Max.: 20.0 s
b5-17 PID Target Selection
0
∶
PID Target Disabled
1
∶
PID Target Enabled
Default
∶
0
Min.: 0
Max.: 1
b5-18 PID Target Value
Sets the PID target value as a percentage of the
maximum output frequency when b5-17 is set to
1. Disabled when b5-17=0
Default
∶
0.00%
Min.: 0.00%
Max.: 100.00%
b5-19
PID Target Value
Units
0
∶
0.01Hz
1
∶
0.01% (Maximum Frequency is 100%)
2
∶
r/min. (Number of Motor Poles must be set)
3
∶
User Defined (Defined by b5-24 and b5-25)
Default
∶
1
Min.: 0
Max.: 3
b5-20 PID output lower
The lower limit value can be set to avoid the
Default
∶
0.0%
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...