123
Keypad
Display
Fault Name
Cause
Possible Solution
when E1-
口口
= 40
input terminal (S1to S8)
HCA
Current Alarm
Drive current exceeded
the level of over current
warning (150% of the
rated current)
1. The load is too heavy
2. Deceleration and
acceleration times are too
short
3.The drive is attempting to
run a motor greater than
the maximum allowable
capacity, or a
special-purpose motor is
being used
4.The current level went up
because of Speed Search
while attempting to perform
a fault restart or after a
momentary power loss
1. Reduce the load or use a drive of
higher rating
2. Calculate the torque required
during acceleration and the inertia
»Take the following steps if the
torque level is not right for the load
· Increase the settings for
acceleration and deceleration time
(C1-00 to C1-07)
· Use a drive of higher rating
3. Check the motor capacity
· Make sure the motor capacity is
right for the drive rating.
4. During a momentary power loss
or an attempt to reset a fault, the
alarm is displayed. However, there
is no need to take any action
because the fault display will
disappear shortly
DNE
Driver Enable
1. The multi-function
contact input function is set
to 69/169, but the contact
input status is incorrect.
2. Multi-function contact
input setting is incorrect
1. Put the input function of the
setting function to 69
2. Disconnect the input contact
with the setting function of 169
AnL
Analog signal(A2) loss
1. Analog A2 signal
disconnection
1. Please check the analog signal
wiring
2. Please confirm the E3-10
parameter setting.
ES
Emergency Stop
1. After the emergency stop
function is turned on before
power off (P2-11), the DC
bus voltage is lower than
P2-06.
2. Multi-function contact
1. Turn off the emergency stop
function P2-11 before power off,
and adjust the P2-06 setting level.
2. Please confirm the multi-function
contact input function setting and
terminal status
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...