104
Parameter
Name
Description
Setting Range
suppression current
value
(overcurrent) or oL1 (motor overload) and oL2
(drive overload) occur, reduce the n3-06 setting.
(The inverter rated current is 100%)
Min.: 0
Max.: 150%
Group o, Keypad Function Settings
o1: Display Setting
o1-00
Frequency Command
Setting/Display Unit
0 : Use units of 0.01 Hz
1 : Use units of 0.01% (100% as maximum output
frequency)
2 : Use units of min-1 (automatically calculated by
maximum output frequency and number of motor
poles)
3 : Use user-defined units (defined by o1-02 and
o1-03)
Default: 0
Range: 0 to 3
o1-01
<7>
Sets unit of
frequency-related
parameters of V/f
characteristics
0: in Hz
1: in min -1 (r/min)
Default: 0
Range: 0,1
o1-02
User-Defined
Frequency Command
Setting/Display
1 to 60000
Default: Determined by
o1-00
Min.: 1
Max.: 60000
o1-03
Frequency
Command
Setting/Display
Decimal Places
0 to 3
Default: Determined by
o1-00
Min.: 0
Max.: 3
o2: Multi-Function Selection
o2-00
LO/RE
(LOCAL/REMOTE)
Key Function
Selection
Enables or disables LO/RE key on the keypad.
0
∶
Disabled
1
∶
Enabled
Switches between Local and Remote Operation
Default: 1
Range: 0, 1
o2-01
STOP Key Function
Selection
Enables or disables the STOP key on the keypad
when the drive is controlled from a remote
source.
0
∶
Disabled
1
∶
Enabled
The STOP key always stops drive operation even
if the command source is not set to the keypad.
Default: 1
Range: 0, 1
o2-02
Retain
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...