4.3.3 Control Circuit Cable Size and Tightening Torque
Select the cable according to Table 4.3.3.1. Use crimp ferrules on the cable ends for simpler and
more reliable wiring.
Table 4.3.3.1 Cable Size and Tightening Torque
Terminal
Screw
Size
Tightening
Torque
Nm
( lb.in.)
Bare Cable
Ferrule-Type Terminal
Cable
Type
Applicable Size
mm2
( AWG)
Suggested Size
mm2
( AWG)
Applicable Size
mm2
( AWG)
Suggested Size
mm2
( AWG)
V-,24V,S1,S2,S3,S4,S5,S6
,S7,S8,DC,D1,D2
V+,COM,A1,A2,FM,AM,A
C,MT,RP,PC,MP,PC,PE
M2
0.23
(2.0)
0.13 to 1.31
(26 to 16)
0.13
(26)
0.13 to 0.33
(26 to 22)
0.13
(26)
Shielded
cable, etc.
R1A, R1B, R1C, R2A, R2C
M2.6
0.59
(5.2)
0.13 to 2.08
(26 to 14)
0.13
(26)
0.13 to 0.33
(26 to 22)
0.13
(26)
Shielded
cable, etc.
4.3.4 Ferrule-Type Terminals
Always use ferrule-type terminals with insulated sleeves. Refer to Table 4.3.3.2. for dimensions. In
addition, crimping tool CRIMPFOX ZA-3 manufactured by Phoenix Contact is recommended.
Table 4.3.3.2 Ferrule-Type Terminal Models and Sizes
Cable Size
mm2 ( AWG)
Type
L
( mm)
d1
( mm)
d2
( mm)
Manufacturer
0.25 ( 24)
AI 0.25-6YE
10.5
0.8
2
Phoenix Contact
0.34 ( 22)
AI 0.34-6TQ
10.5
0.8
2
Phoenix Contact
0.5 ( 20)
AI 0.56-WH
14
1.1
2.5
Phoenix Contact
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...