143
BIT 1
1: Reverse running
BIT 2
1: Zero speed
BIT 3
1: malfunction
BIT 4
1: caution
BIT 5
1: Consistent frequency
BIT 6
1: The inverter is ready to run.
BIT 7
1: Frequency provided by communication
BIT 8
1: Operation provided by communication
BIT 9
1: Torque mode
BIT 10
1: Zero servo mode
BIT 11~15
Retain
2422H Frequency command (Unit 0.01Hz)
2423H Output frequency (Unit 0.01Hz)
2424H Output current (Unit 0.01A)
2425H output voltage (Unit 0.1V)
2426H DC voltage (Unit 0.1V)
2427H Warning description
2428H Fault description
2429H
Multi-function input and output status
BIT 0
1: Multi-function terminal 1 ON
BIT 1
1: Multi-function terminal 2 ON
BIT 2
1: Multi-function terminal 3 ON
BIT 3
1: Multi-function terminal 4 ON
BIT 4
1: Multi-function terminal 5 ON
BIT 5
1: Multi-function terminal 6 ON
BIT 6
1: Multi-function terminal 7 ON
BIT 7
1: Multi-function terminal 8 ON
BIT 8~10
Retain
BIT 12
1: Relay1 ON
BIT 13
1: Relay2 ON
BIT 14
1: PH1 ON
BIT 15
Retain
242A
H
AI1 Input (0 correspond 0V or 0mA, 1000 correspond 10V or 20mA)
242B
H
AI2 Input (0 correspond 0V or 4mA, 1000 correspond 10V or 20mA)
242C Retain
Summary of Contents for EVO 8000 Series
Page 1: ......
Page 3: ...7 4 MODBUS Data List 142 APPENDIX UL DESCRIPTION 156...
Page 15: ...12 2 2 Nameplate Model Number Applicable motor rating Input power supply Output power supply...
Page 48: ...45 4 3 2 1 Multi Function Digital Input Wiring Diagram...
Page 49: ...46 4 3 2 2 Pulse input wiring diagram...
Page 55: ...52 F1 F4 F5 F6 Figure 4 4 4 DIP Switch RS 485 Termination Resistor OFF ON...
Page 169: ...166 22F 392 Ruey Kung Road Neihu Taipei City 114 Taiwan...