Contact at P304
Signal
Cable colour
B-FLT
Fault
SEC
II
-
COM
(changeover)
[WH]
B-FLT
Fault
SEC
II
-
NC
(normally closed) /
NO
(normally open)
[BN]
B-ALM
Alarm
SEC
II
-
NC
(normally closed) /
NO
(normally open)
[BN]
B-ALM
Alarm
SEC
II
-
COM
(changeover)
[WH]
Table 20: Pin assignment at
P304
In case of an alarm, the alarm relays signal the exceeding of the set differential and/or maximum temperature
threshold values at cable connection
I
/
II
.
In case of a fault, the fault relays signal malfunctions of the sensor control unit
SCU 835
, the sensor cables
SEC 15
and the individual sensors
ESD-A5
to cable connection
I
/
II
.
Normal state – device in operation:
Relay contact at the Mainboard
SCI 835
Relay /
LED
state
Alarm relay
P305
-
A-ALM
Switched off - no alarm at
I
Fault relay
P305
-
A-FLT
Switched on - no fault at
I
Alarm relay
P304
-
B-ALM
Switched off - no alarm
at
II
Fault relay
P304
-
B-FLT
Switched on - no fault at
II
Table 21: Displays normal state
Alarm / fault state – device in operation:
Relay contact at the Mainboard
SCI 835
Relay /
LED
state
Alarm relay
P305
-
A-ALM
Switched on - alarm at
I
Fault relay
P305
-
A-FLT
Switched off - fault at
I
Alarm relay
P304
-
B-ALM
Switched on - alarm at
II
Fault relay
P304
-
B-FLT
Switched off - fault at
II
Table 22: Displays alarm / fault state
Note
If the unit is
not
in operation, the fault relay fails and a fault is indicated at the
FACP
.
Optionally, the relay contacts on the two
14-pin IC
sockets can be equipped with a
0 Ω
bridge or with loop resistors
for closed-circuit current monitoring
R*
.
Max. switching current
Max. switching voltage
Max. switching power
Relays at
MB SCI 835
1 A
+30 V DC
30 W
Table 23: Relay outputs
60T328-02-LI-en / 29.01.2021
LISTEC GmbH
Page 53/112
Fig. 105: Alarm as
NO
/ fault as
NO
Fig. 106: Alarm / fault with loop resistors
R*
B-ALM
A-FLT
A-ALM
B-FLT
II
I
B-ALM
B-FLT
A-FLT
A-ALM
II-R*
I-R*