Chapter 5 - Parameter Description (I/O Group)
75
I/O 41: Speed Display Multiplier Factor
I/O 40: Speed Display Divider Factor
I/O
¢º
Mul factor
41 100
Setting Range:
0 to 999
Factory Default:
100
I/O
¢º
Div factor
42 100
Setting Range:
1 to 999
Factory Default:
100
[I/O 41] and [I/O 42] are used to translate [DRV 04]
into line or process speed. Motor poles are defined in
[FUN 54]. The following equation may be used to
determine the proper output.
I/O 43: Input Terminal Status
I/O 44: Output Terminal Status
I/O
¢º
Ter. input
43 1000000001
I/O
¢º
Ter. output
44 10001
[I/O 43] and [I/O 44] displays the status of FX, RX,
P1 – P6 input terminals and OC1, OC2, OC3, AUX1
(1A, 1B) and AUX2 (2A, 2B) output terminals.
Input Terminal Status
P6
P5
P4
P3
P2
P1
X
X
RX
FX
1
0
0
0
0
0
0
0
0
1
0: OFF, 1: ON
Output Terminal Status
AUX2 AUX1
OC3
OC2
OC1
1
0
0
0
1
0: OFF, 1: ON
I/O 45: Software Version
I/O
¢º
S/W
version
45 1.00H
[I/O 45] displays the software version of the inverter.
I/O 46: Fault History 1
I/O 47: Fault History 2
I/O
¢º
Last fault 1
46 OV Trip
I/O
¢º
Last fault 2
47 OC Trip
[I/O 46] and [I/O 47] review trip information. By
using keypad, trip information (Over Current, Over
Voltage and Frequency) may be displayed.
Example:
By using the PROG, UP and DOWN arrow key, old trip
information (which contains current, frequency and trip) can be
viewed.
I/O
¢º
Last fault 1
46 OV Trip
I/O
¢º
Last fault 1
46 35.60 Hz
I/O
¢º
Last fault 1
46 16.5 A
I/O
¢º
Last fault 2
47 OC Trip
Line Speed =
Multiplier Factor
Divide Factor
×
120 * Output Frequency
P (Number of Poles)
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...