Chapter 4 - Parameter List
34
Code
[FUN]
Description
Function Group
Keypad Display
Setting Range
Units
Factory
Default
Adj.
During
Run
Page
12
Deceleration Pattern
Dec. pattern
Linear,
S-Curve,
U-Curve
-
Linear
No
47
13
Output Voltage Adjustment
Volt control
40 to 110 [%]
1
100 [%]
No
47
14
Energy Savings Level
Energy save
30 to 100 [%]
1
100 [%]
Yes
48
15
Stop Mode Selection
Stop mode
Decel,
DCBR,
Free Run
-
Decel
No
48
16
User V/F - Frequency 1
User-1f
0 to 30 [Hz]
0.01
10.00 [Hz]
No
49
17
User V/F - Voltage 1
User-1v
0 to 50 [%]
1
15 [%]
No
49
18
User V/F - Frequency 2
User-2f
FUN 16 to
FUN 04
1
30.00 [Hz]
No
49
19
User V/F - Voltage 2
User-2v
FUN 17 to 100 [%]
1
50 [%]
No
49
20
Analog Speed Input Selection
V-I mode
V1,
I,
V1 + I,
V2
-
V1
No
49
21
Analog Speed Input Filter Gain
Filter gain
1 to 100 [%]
1
25 [%]
Yes
50
22
Analog Speed Input Gain
Analog gain
50 to 250 [%]
1
100 [%]
Yes
50
23
Analog Speed Input Bias
Analog bias
0 to 100 [%]
1
0 [%]
Yes
50
24
Analog Speed Input Direction
Analog dir
Direct,
Invert
-
Direct
Yes
50
25
Frequency Limit Selection
Freq. limit
No,
Yes
-
No
No
52
26
Frequency High Limit Selection
F-limit high
0 to FUN 04
0.01
60.00 [Hz]
No
52
27
Frequency Low Limit Selection
F-limit low
0 to FUN 26
0.01
0.00 [Hz]
No
52
28
Jump Frequency Selection
Freq. jump
No,
Yes
-
No
No
52
29
Jump Frequency 1
Freq-jump 1f
0 to FUN 04
0.01
10.00 [Hz]
No
52
30
Jump Frequency 2
Freq-jump 2f
0 to FUN 04
0.01
20.00 [Hz]
No
52
31
Jump Frequency 3
Freq-jump 3f
0 to FUN 04
0.01
30.00 [Hz]
No
52
32
Jump Frequency Bandwidth
Freq. band
0 to 30 [Hz]
0.01
5.00 [Hz]
No
52
33
DC Injection Braking Frequency
DC-br freq
0 to 60 [Hz]
0.01
0.5 [Hz]
Yes
53
34
DC Injection Braking On-Delay
Time
DC-br block
0.5 to 5 [sec]
0.1
2 [sec]
Yes
53
35
DC Injection Braking Time
DC-br time
0.1 to 250 [sec]
0.1
0.5 [sec]
Yes
53
36
DC Injection Braking Voltage
DC-br value
1 to 20 [%]
1
1 [%]
Yes
53
37
Slip Compensation
Slip compen.
No,
Yes
-
No
Yes
54
38
Rated Motor Slip
Rated slip
0 to 5 [Hz]
0.01
0.00 [Hz]
Yes
54
39
Rated Motor Current (RMS)
M-rated cur.
0.1 to 999 [A]
0.1
103.0 [A]
1
Yes
54
1
Default value will depend on the inverter capacity.
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...