Chapter 5 - Parameter Description (Function Group)
57
[Stall Prevention during ‘Steady’]
[Stall Prevention during ‘Deceleration’]
FUN 47: Overload Warning Level
FUN 48: Overload Warning On-Delay Time
FUN
¢º
OL level
47 150 %
Setting Range:
30 to 150%
Factory Default:
150%
FUN
¢º
OL time
48 10.0sec
Setting Range:
1 to 30 sec
Factory Default:
10sec
[FUN 47] is used to provide motor overload
detection. When the output current of the inverter has
reached the “Overload Warning Level” and after the
[FUN 48] on-delay time has been reached, a multi-
output signal may be turned on.
For example, define multi-output OC1 in [I/O 07 ~
09] (OC1 Output) to OL. The multi-output is open
collector (24V DC, 50mA).
[Overload Warning]
FUN 49: Over Current-Limit Trip Level
FUN 50: Over Current-Limit Trip Time
FUN
¢º
OC lim level
49 160 %
Setting Range:
CT: 30 to 200%
VT: 30 to 150%
Factory Default:
160%
Output Current
Time
Output Frequency
Time
FUN 46
[Stall level]
FUN 46
[Stall level]
OC1 OC2 OC3 EG
Open Collector Outputs
(24VDC, 50mA)
OL
24V DC
Supply
Relay
+
Output Current
Time
Time
FUN 47
[OL level]
FUN 47
[OL level]
OC1-EXTG
ON
t1
t2
t1: Overload warning time - FUN 48 [OL time]
t2: Overload warning time / 2
Output Current
Time
Output Frequency
Time
FUN 46
[Stall level]
FUN 46
[Stall level]
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...