Chapter 5 - Parameter Description (Function Group)
52
FUN 25: Frequency Limit Selection
FUN 26: High Limit Frequency
FUN 27: Low Limit Frequency
FUN
¢º
Freq. limit
25 --- No ---
Setting Range:
No, Yes
Factory Default:
No
FUN
¢º
F-limit high
26 60.00 Hz
Setting Range:
0 to FUN 04 [Freq. max]
Factory Default:
0%
FUN
¢º
F-limit low
27 0.00 Hz
Setting Range:
0 to FUN 26 [F-limit high]
Factory Default:
0%
[FUN 25] selects the limits for the inverter operating
frequency. If [FUN 24] is set to ‘Yes’, the inverter
operates within the upper and lower limit setting.
The inverter operates at the upper or the lower limit
when the frequency reference is outside the
frequency limit range.
[Freq. limit: ‘Yes’]
n
Note:
When setting the frequency below the low limit or
above the high limit, the drive will automatically ramp inside
the limited setting.
n
Note:
When accelerating or decelerating, the output
frequency follows the normal acceleration and deceleration
rates.
FUN 28: Frequency Jump Selection
FUN 29: Frequency Jump 1
FUN 30: Frequency Jump 2
FUN 31: Frequency Jump 3
FUN 32: Frequency Jump Bandwidth
FUN
¢º
Freq. jump
28 --- No ---
Setting Range:
No, Yes
Factory Default:
No
FUN
¢º
Freq-jump 1f
29 10.00 Hz
Setting Range:
0 to FUN 04 [Freq. max]
Factory Default:
10Hz
FUN
¢º
Freq-jump 2f
30 20.00 Hz
Setting Range:
0 to FUN 04 [Freq. max]
Factory Default:
20Hz
FUN
¢º
Freq-jump 3f
31 30.00 Hz
Setting Range:
0 to FUN 04 [Freq. max]
Factory Default:
30Hz
FUN
¢º
Freq. band
32 5.00 Hz
Setting Range:
0 to 30Hz
Factory Default:
5Hz
To prevent undesirable resonance and vibration on
the structure of the machine, this function locks out
the resonance frequency from occurring.
Each jump frequency also has a bandwidth. This is a
span of the particular jump frequency selected. Three
different jump frequencies can be set. However,
there is only one bandwidth frequency available.
Output Frequency
Freq. Max
Time
FUN 25
FUN 26
Reference Frequency Curve
Output Frequency Curve
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...