Chapter 5 - Parameter Description (Function Group)
54
[FUN 33] (DC Injection Braking Frequency) is the
frequency at which the inverter starts to output DC
voltage during deceleration.
[FUN 34] (DC Injection Braking On-Delay Time) is
the inverter output blocking time before DC injection
braking.
[FUN 35] (DC Injection Braking Time) is the time
the DC current is applied to the motor.
[FUN 36] (DC Injection Braking Voltage) is the DC
voltage applied to the motor and is based upon rated
inverter output voltage.
FUN 37: Slip Compensation
FUN 38: Rated Slip of Motor
FUN 39: Rated Current of Motor
FUN 40: No Load Current of Motor
FUN
¢º
Slip compen.
37 --- No ---
Setting Range:
No, Yes
Factory Default:
No
FUN
¢º
Rated slip
38 0.00 Hz
Setting Range:
0 to 5Hz
Factory Default:
0Hz
FUN
¢º
M-rated cur.
39 122.0 A
Setting Range:
0.1 to 999A
Factory Default:
depend on [FUN 41]
FUN
¢º
No-load cur.
40 0.1 A
Setting Range:
0.1 to 300A
Factory Default:
4.0A
This function is used to maintain the motor speed
constantly. To keep the motor speed constant, the
output frequency varies within the limit of slip
frequency-FUN 38 [Rated slip] according to the load
current. For example, when the motor speed
decreases below the reference speed (frequency) due
to a heavy load, the inverter increases the output
frequency higher than the reference frequency to
increase the motor speed. The inverter increases or
decreases the output by delta frequency shown
below.
Output frequency = Reference freq. + Delta freq.
FUN 41: Inverter Capacity
FUN
¢º
Inv Capacity
41 SV030iH-2
Setting Range:
SV030iH-2U ~ SV220iH-4U
Factory Default:
depend on model number
Description:
[FUN 41] selects the inverter capacity. Inverter
capacity must be set correctly for proper current
calculation and protective functions.
FUN 42: Auto Restart
FUN 43: Restart On-Delay Time
FUN
¢º
Retry number
42 0
Setting Range:
0 to 10
Factory Default:
0
Delta
Freq.
=
Output Current – No-load Current
Rated Current – No-load Current
Rated
Slip
×
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...