Chapter 1 - Installation
14
1.7.2
Terminal Configuration
A Dynamic Braking Unit or a DC Bus Choke or both of them may be added to iH series inverters.
Jumper Between P1 and P2 Must Be Removed In Order
To Install a DC Bus Choke.
R
S
T
G
U
V
W P1 P2 N
Fig. 1
– Type C Dynamic Braking Unit, DC Bus Choke Installation
WARNING
Normal stray capacitance between the inverter chassis and the power devices inside the
inverter and AC line can provide a high impedance shock hazard. Refrain from applying
power to the inverter if the inverter frame (Power terminal G) is not grounded.
!
!
Motor
3 Phase
Power Input
Dynamic
Braking
Unit
Dynamic Braking Resistor
DC Bus Choke
Refer to DB Unit Manual for
detailed terminal configuration