Chapter 4 - Parameter List
35
Code
[FUN]
Description
Function Group
Keypad Display
Setting Range
Units
Factory
Default
Adj.
During
Run
Page
40
No Load Motor Current in RMS
No-load cur.
0.1 to 300 [A]
0.1
0.1 [A]
Yes
54
41
Inverter Capacity
Inv Capacity
SV030iH-2U
SV037iH-2U
···
···
SV315iH-4U
SV375iH-4U
-
SV030iH-2
2
No
54
42
Number of Auto Restart attempt
Retry number
0 to 10
1
0
Yes
54
43
Delay Time Before Auto Restart
Retry time
0 to 10 [sec]
1
1 [sec]
Yes
54
44
Fault Output Relay (A, C, B)
Relay mode
Retry 0,
All Trips,
LV + Retry 0,
LV + All Trips
-
Retry 0
Yes
55
45
Stall Prevention Mode
Stall mode
None,
Acc,
Steady,
Acc + Steady,
Dec,
Acc + Dec,
Dec + Steady,
Acc + Dec+
Steady
-
None
Yes
55
CT: 30 to 150 [%]
1
150 [%]
Yes
55
46
Stall Prevention Level
Stall level
VT: 30 to 150 [%]
1
110 [%]
Yes
CT: 30 to 150 [%]
1
150 [%]
Yes
47
Overload Warning Level
OL level
VT: 30 to 110 [%]
1
110 [%]
Yes
57
48
Overload Warning Hold Time
OL time
1 to 30 [sec]
1
10 [sec]
Yes
57
CT: 30 to 200 [sec]
1
160 [%]
Yes
49
Over Current Trip Limit Level
OC lim level
VT: 30 to 150 [sec]
1
110 [%]
Yes
57
50
Over Current Limit Time
OC lim. Time
0 to 60 [sec]
0.1
60 [sec]
Yes
57
51
Electronic Thermal Selection
ETH select
No, Yes
-
No
Yes
58
52
Electronic Thermal Level
ETH level
30 to 150 [%]
1
150 [%]
Yes
58
53
Electronic Thermal Characteristic
(Motor Type) Selection
Motor type
General,
Special
-
General
Yes
58
54
Number of Motor Poles
Pole number
2 to 12
1
4
Yes
59
55
IPF (Instant Power Failure)
Restart Selection
IPF select
No,
Yes
-
No
Yes
59
56
Speed Search Acceleration Time
SS acc. time
0.1 to 600 [sec]
0.1
5 [sec]
Yes
59
57
Speed Search Deceleration Time
SS dec. Time
0.1 to 600 [sec]
0.1
10 [sec]
Yes
59
58
Speed Search Gain
SS gain
0 to 200 [%]
1
100 [%]
Yes
59
2
FUN 41 is set at its inverter capacity before shipping outside. However, inverter loses its capacity after parameter initialization in FUN 97. If the
parameters are initialized, be sure to re-set the inverter capacity to the right capacity.
Summary of Contents for SV030iH-2U
Page 26: ...Chapter 2 Operation 24 Blank Page...
Page 34: ...Chapter 3 Quick Start Procedures 32 Blank Page...
Page 42: ...Chapter 4 Parameter List 40 Blank Page...
Page 66: ...Chapter 5 Parameter Description Function Group 64...
Page 67: ...Chapter 5 Parameter Description Function Group 65 Blank Page...
Page 81: ...Chapter 5 Parameter Description I O Group 79 Blank Page...