Temperature sensor(2TH) setting (air conditioner / DX ventilator)
It is the function to select the temperature sensor to decide the indoor temperature.
• You can set the following setting values using [<,>(left/right)] button.
• 2TH function’s operation characteristics may be different for each product.
Temperature sensor location
Description
Remote controller
Operate the system with wired remote controller’s temperature
sensor
Indoor Unit
Operate the system with indoor unit’s temperature sensor
2TH
Cool
Compare the temperatures of the indoor unit and the wired re-
mote controller and operate with the higher temperature
(There are system operated with lower temperature)
Heat
Compare the temperatures of the indoor unit and the wired re-
mote controller and operate with the lower temperature
Ceiling height setting (air conditioner)
It is the function to control the fan speed stage according to the ceiling height in the ceiling type
product.
• You can set the following setting values using [<,>(left/right)] button.
Ceiling height
Description
Low
Fan speed operates one step slower than the default value.
Standard
Operates at the default fan speed
High
Fan speed operates one step faster than the default value.
Very high
Fan speed operates two steps faster than the default value.
NOTE
!
When group control is enabled some functions are limited depending on product type.