INSTALLER SETTING
120
INSTALLER SETTING
ENGLISH
Central control address setting (air conditioner / general, DX
ventilator)
It is the function to set the central control address of the indoor unit to allow communication with
a central controller,
• In the installer setting list, select the central control address setting category, and press [OK]
button to move to the detail screen.
- Select a hex value between 00 and FF.
Value 1: group address setting / value 2: indoor unit address setting
OK
ESP setting (air conditioner / general, DX ventilator)
It is the function to set the fan speed value corresponding to each fan speed for easy installation.
• In the installer setting list, select the ESP setting category, and press [OK] button to move to
the detail screen.
OK
NOTE
!
If ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by the installation specialist that holds an installation license.
For ventilation products, separate ESP values are used for the supply and exhaust fans.
NOTE
!
Be especially careful not to switch ESP values corresponding to each fan speed.
Engineering manuals have ESP setting tables that reference air flow and corresponding
value setting to achieve the flow.
The ESP values that can be set may be different for each product and capacity.
Product
ESP fan speed
value
Air conditioner
Slow
0 ~ 255
Low
Med
High
Power
Ventilation
Low
High
Power