111
INSTALLATION
110
INSTALLATION
ENGLISH
• When you remove the remote controller from the installation plate, insert a small flat head screw-
driver into the bottom side separation hole and turn clockwise to separate the remote controller.
- There are 2 separation holes at the bottom part. Slowly separate one by one.
- Be careful not to damage the internal parts during the removal.
<Order of Separation>
• Use the connection cables to connect the indoor unit with the remote controller.
• For the following cases, separately purchase and use the cables suitable for the situation.
- Do not install the cable over 50 m. (It may cause communication issues.)
- If the distance between the wired remote controller and the indoor unit is 10 m or more : 10
m extension cable (model name: PZCWRC1)
- If you control several indoor unit products with one wired remote controller : Group control
cable (model name: PZCWRCG3)
Please check if connector is normally connected.
Connecting cable
Indoor
Unit side
OK
DC 12 V
Red
Signal
Yellow
GND
Black
Group control
• It connects and controls 2 or more air conditioner indoor units(Maximum number of IDU : 16ea)
to one wired remote controller.
※
Connect using the group control cable.
①
Group control cable (PZCWRCG3): Connect to indoor unit’s wired remote controller connector
②
Extension cable (PZCWRC1): Connect to No.
①
cable and slave indoor unit’s wired remote
controller connector
While No.
①
cable is connected, connect No.
②
cable.
• After checking the existence of the event communication in the product manual, change
master/slave of the remote controller.
※
For details, refer to ‘remote controller master/slave’ contents.
• Change master/slave of the indoor unit.
- For ceiling cassette and duct product group, change the setting with the indoor unit PCB
switch.
RED(12V)
YELLOW(SIG)
BLACK(GND)
YELLOW(SIG)
BLACK(GND)
YELLOW(SIG)
BLACK(GND)
OK
Indoor unit Main PCB
Indoor unit 1
Indoor unit 2
Indoor unit 3
Master
Slave
Slave
1
2
NOTE
!
• Connect only GND and signal cable to the indoor unit set as slave. (If power cable is also
connected, it may cause loss of communication)
• Inquiries related to the purchase of the cable shall be directed to the specialized company
and the service center.
Master
Slave Slave
GND
GND
12V
Signal cable
Signal cable
Black
Red
No. 3 switch OFF: master (factory ship-out based)
No. 3 switch ON: slave
Yellow
Yellow
Yellow
OK
NOTE
!
During the wired remote controller installation, do not bury it in the wall. (It may cause
temperature sensor failure.)
Do not install the cable over 50 m. (It may cause communication defect.)
When you install the extension cable, carefully check the direction of the connectors on the
remote controller side and the product side before the installation.
Specification of extension cable: AWG 24, 3 conductor or above.
W
a
ll Side
• After fixing the remote controller top side on the installation plate attached to the wall as in the
following figure, press the bottom side to combine with the installation plate.
- Do not leave a gap in the top, bottom, left, and right side of the remote controller and the in-
stallation plate after combining them.
- Before combining with the installation plate, arrange the cables to avoid interference with the
circuit parts.
<Order of Combining>
Wall
Wall