86
FUNCTION SETTING
87
USER SETTING
ENGLISH
USER SETTING
How to enter user setting
To enter the menu displayed at the bottom, you need to enter the user setting menu as follows.
• Select the setting category, and press [OK] button to move to the setting list.
• Select the user setting category, and press [OK] button to move to the user setting list.
User Setting
• You can set the product user functions.
• Some functions may not be available in some product types.
OK
Menu
Description
Language setting
Set the language to be displayed on the remote controller.
Setpoint Type Setting
It is the function to set GUI type on the remote controller.
Temperature unit setting
Set the temperature unit displayed on the remote controller.
Screen saver timer setting
Adjust the screen Off time of the remote controller.
LCD brightness in idle setting Adjust the remote controller’s screen brightness.
External device setting
Set the name of external equipment and equipment logic setting
Date setting
Set the date displayed on the remote controller.
Time setting
Set the time displayed on the remote controller.
Summer time setting
Set the summer time in the remote controller.
Password setting
Set the password to prevent unauthorized change to remote controller settings.
Schedule initialization
Initialize all timer settings in the remote controller.
Theme setting
Set the theme of the remote controller screen.
Humidity display
It is the function to decide whether to display humidity on the main
screen and additional information screen.
System reboot
Restart the remote controller.
Indoor unit display light
brightness
This function adjusts the brightness of the indoor unit display light.
OK
Condition 1
Condition 2
Operation on
Off
Low
Periodic
Operation off
Off
Periodic
Value
Description
Off
Disable the economizer function to keep the outside air damper closed.
Auto
If the outside air temperature is lower than the air temperature indoors when
cooling is being operated, outside air is supplied to the room to save energy.
Step 1
Opens the outside air damper opening by one stage to improve the indoor
air quality by introducing fresh air into the room.
Step 2
Opens the outside air damper opening by two stages to improve the indoor
air quality by introducing fresh air into the room.
NOTE
!
Economizer setting function may not be available on some products.
Economizer setting
Provides outside air to a room to save energy and improve the air quality indoors.
CO
2
Fan Control(general ventilator)
A function that controls the fan when the product is turned ON/OFF, based on the CO
2
concentration in the ventilation product.
1
. After selecting “CO
2
fan control” in the Function settings list, press the [OK] button to go to the detail screen.
2
. After selecting “Fan control during operation on” or “Fan control during operation off” in the "
CO
2
Fan Control" list, you can set the following values using [<,>(left/right)] button.
Summary of Contents for PREMTB100
Page 82: ......