Service Manual 287
No
No
No
No
No
Yes
Do you feel
initialization vibration when
applying initial power?
Start of check.
Replace the PCB.
Outdoor Unit LEV.
No failure of outdoor unit LEV.
Yes
Yes
Yes
Yes
Is power supplied to the
outdoor unit LEV?
Replace the check valve.
Is the check valve normal?
Replace the
outdoor unit LEV
• It is difficult to separate coils and the main
body for the outdoor unit LEV,
and it is impossible to mount them again.
Is there temperature
difference between front end and
rear end of LEV in
cooling operation?
Is there temperature
difference between front end and
rear end of LEV in
heating operation?
Self-diagnosis function