250
Trouble Shooting Guide
Checking Method for Key Components
LEV
M
1
3
2
6
4
ø5
Red
White
Yellow
Orange
Blue
5
4
3
2
ø4
DC 12V
Driving
circuit
ø3
ø2
ø1
1
ø4
ø3
ø2
ø1
• Pulse signal output value and valve operation
• Output pulse sequence
- In valve close state: 1
→
2
→
3
→
4
→
5
→
6
→
7
→
8
→
1
- In valve open state: 8
→
7
→
6
→
5
→
4
→
3
→
2
→
1
→
8
* 1. If LEV open angle is not change, all of output phase will be OFF
2. If output phase is different or continuously in the ON state, motor will not operate smoothly and start
vibrating.
• LEV valve operation
ø1
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
ø2
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ø3
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ø4
OFF
OFF
OFF
OFF
ON
ON
ON
OFF
Output(ø) No.
Output state
1
2
3
4
5
6
7
8
Valve
open
Angle
close
pulse
open
Full open
1950 pulses
- At power ON, open angle signal of 2000 pulses out-
put and valve position is set to
If valve is operated smoothly, no noise and vibration
is occurred and if valve is closed. noise occurs.
- If you contact screw driver to LEV, and contact your
ear to driver hand grip. you can confirm the noise
from LEV.
- If liquid refrigerant is in LEV, the noise is lower.
2.3 Linear Empansion Valve
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...