302
Trouble Shooting Guide
Voltage-Pressure Table
High pressure sensor
3500
3000
2500
2000
1500
1000
500
0
0
0.5
1.5
2.5
3.5
1
2
3
4
YSK S345 sensor
Voltage, V
Pressure
, kP
a abs
Voltage, V
P, kPa
Tbub, °C
Voltage, V
P, kPa
Tbub, °C
Voltage, V
P, kPa
Tbub, °C
1.28
881
14.3
2.06
1661
38.0
2.84
2441
54.4
1.31
911
15.5
2.09
1691
38.7
2.87
2471
54.9
1.34
941
16.6
2.12
1721
39.4
2.9
2501
55.5
1.37
971
17.7
2.15
1751
40.2
2.93
2531
56.0
1.4
1001
18.8
2.18
1781
40.9
2.96
2561
56.5
1.43
1031
19.8
2.21
1811
41.5
2.99
2591
57.1
1.46
1061
20.9
2.24
1841
42.2
3.02
2621
57.6
1.49
1091
21.9
2.27
1871
42.9
3.05
2651
58.1
1.52
1121
22.9
2.3
1901
43.6
3.08
2681
58.6
1.55
1151
23.8
2.33
1931
44.2
3.11
2711
59.1
1.58
1181
24.8
2.36
1961
44.9
3.14
2741
59.6
1.61
1211
25.7
2.39
1991
45.5
3.17
2771
60.1
1.64
1241
26.6
2.42
2021
46.1
3.2
2801
60.6
1.67
1271
27.5
2.45
2051
46.8
3.23
2831
61.1
1.7
1301
28.4
2.48
2081
47.4
3.26
2861
61.6
1.73
1331
29.3
2.51
2111
48.0
3.29
2891
62.1
1.76
1361
30.1
2.54
2141
48.6
3.32
2921
62.6
1.79
1391
31.0
2.57
2171
49.2
3.35
2951
63.1
1.82
1421
31.8
2.6
2201
49.8
3.38
2981
63.5
1.85
1451
32.6
2.63
2231
50.4
3.41
3011
64.0
1.88
1481
33.4
2.66
2261
51.0
3.44
3041
64.5
1.91
1511
34.2
2.69
2291
51.6
3.47
3071
64.9
1.94
1541
35.0
2.72
2321
52.1
3.5
3101
65.4
1.97
1571
35.8
2.75
2351
52.7
2
1601
36.5
2.78
2381
53.3
2.03
1631
37.3
2.81
2411
53.8
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...