254
Trouble Shooting Guide
Checking Method for Key Components
P
N
U
V
W
3
7
11
16
17
18
P
N
U
V
W
1
19
Array of IPM Pin
If one of the above articles is not satisfied,
IPM must be inferior and is to be replaced
Internal circuit diagram
Appearance
1. Unplug the +, – terminal of electrolytic capacitor from the P and N terminal of
IPM
2. Set the multi meter to resistance mode
Check and estimate the resistance between each pair of terminal
(P, N), (P, U), (P, V), (P, W), (U, N), (V, N), (W, N), the estimated value should be
large enough to Mega Ohm unit.
3. Set the multi meter to resistance mode
Check and estimate the resistance between each pair of terminal
(3, U), (7, V), (11, W), (16, N), (17, N), (18, N), the estimated value
should be large enough to Mega Ohm unit.
the check point is inside of the screw hole (U, V, W, N), if check points are plate
face of the terminal, then estimated values are gate resistance.
4. Set the multi meter to diode mode, and estimate between each pair of
terminal (U, P), (V, P), (W, P), (N, U), (N, V), (N, W), the estimated value
should be stable and be in between 0 to 1. (ex: 0.35, 0.46 etc.)
In case that the control box is opened and before checking electrical parts,
it should be checked that the LED 01Y (in inverter board, refer to page 172) turned off
(wait 3 minutes after main power OFF), otherwise it may cause electrical shock.
Caution
2.5 IPM(Integrated Power Module)
Summary of Contents for multi V PLUS
Page 21: ...Service Manual 21 Indoor Unit Indoor Units ...
Page 74: ...74 Indoor Unit ...
Page 86: ...86 Indoor Unit ...
Page 142: ...142 Indoor Unit ...
Page 160: ...160 Indoor Unit ...
Page 179: ...Service Manual 179 Outdoor unit ...
Page 239: ...Service Manual 239 Wiring Diagrams 5 8 60Hz 220V Main Outdoor Unit 8HP 10HP 12HP ...
Page 245: ...Service Manual 245 Trouble shooting guide ...
Page 296: ...296 Trouble Shooting Guide ...
Page 297: ...Service Manual 297 Appendix ...
Page 303: ...Service Manual 303 Exploded View Replacement Parts List ...